Heat Stress in Broiler Sheds: What to Measure and When to Stage the Fans

The thermometer on the shed wall reads 31 degrees, and the controller display is green. It is a monsoon afternoon, the sky is grey, and nobody on the farm feels that it is a hot day. Inside, the birds at five weeks are lying flat with their wings held away from their bodies and their beaks open. The next morning the mortality count is several times the usual number.
A week earlier the same shed saw 38 degrees on a dry, bright afternoon. The pads were running, the fans were in tunnel mode, and the flock came through without a mark.
Nothing about this is mysterious once you stop asking what the air temperature is and start asking what the bird can get rid of. A broiler cannot sweat. It sheds heat by warming the air that moves over it and by evaporating water from its airways, and both routes depend on more than the thermometer: on how humid the air is and on how fast it moves. A dry 38 degrees with strong airflow can be easier on a heavy bird than a still, saturated 31.
So the framework for this post is short. Control the shed on what the bird feels, not on what the wall thermometer says. Measure temperature, humidity and air speed together, combine them into one effective index, and stage the fans and pads on that index with enough hysteresis that the equipment does not chatter. Then treat the cold, still night as the other half of the same problem, because that is when ammonia and moisture do their damage.
Why a Broiler Cannot Sweat Its Way Out
A broiler at market weight is a compact heater. Extension guidance for high-density housing puts its heat output at about 15 watts per bird at 41 days. A shed of 20,000 birds is therefore producing about 300 kilowatts of heat before the sun, the roof and the motors add theirs. All of it has to leave through the air.
The bird has two ways to lose that heat. The first is sensible loss: warm skin and feathers heat the air around them, and the moving air carries the heat away. This works only when the air is cooler than the bird, and it works much better when the air moves fast enough to strip the warm layer from the feathers. The second is latent loss: panting evaporates water from the airways and uses the heat of evaporation to cool the blood. This works only when the air can accept more water, which is what relative humidity measures.
On the dry afternoon both routes are open. On the monsoon afternoon the air temperature is closer to the bird's own surface temperature, so sensible loss is weaker, and the air is nearly saturated, so panting achieves little. The bird pants harder, makes more heat doing so, eats less and, if the afternoon lasts long enough, dies.
A broiler loses heat through moving air and through evaporation. Humidity closes the second route, and still air closes most of the first. The thermometer sees neither.
This is the root of most heat-stress losses we hear about in Indian sheds. They are rarely on the hottest days of the year. They cluster in the humid shoulder of the season, before and after the monsoon, when the temperature looks moderate and the controller sees no reason to act.
One Number for Three Variables
Engineers and animal scientists have long tried to fold temperature and humidity into one figure. The family of indices built for this is called the temperature-humidity index, or THI. For broilers, a widely cited form weights the dry-bulb temperature heavily and the wet-bulb temperature lightly: THI equals 0.85 times the dry-bulb temperature plus 0.15 times the wet-bulb temperature, both in degrees Celsius. The wet-bulb temperature carries the humidity information, because it is the temperature a wet surface reaches when water evaporates from it.
Researchers at Iowa State extended the idea with air speed, in work on market-size broilers published in 2003. Their temperature-humidity-velocity index multiplies the THI by the air speed raised to a small negative power, so faster air lowers the effective figure. The exact exponent and the constants vary between studies and breeds, so treat the numbers below as a way to compare conditions, not as a precise physiological threshold.
The script below computes the wet-bulb temperature from temperature and relative humidity using a published approximation, then the THI and the velocity-corrected index. Four conditions typical of an Indian broiler year give these results.
Condition | Air temperature | Relative humidity | Wet-bulb | THI |
Dry summer afternoon | 38 °C | 25% | 23.0 °C | 35.7 |
Pre-monsoon evening | 34 °C | 55% | 26.7 °C | 32.9 |
Monsoon afternoon | 31 °C | 85% | 28.9 °C | 30.7 |
Night after rain | 28 °C | 95% | 27.4 °C | 27.9 |
On THI alone, the dry afternoon still looks worst. That is the point where air speed and cooling equipment change the ranking, and the next two sections show why.
import math
def wet_bulb(t, rh):
# Stull (2011) approximation; t in degC, rh in percent
return (t * math.atan(0.151977 * math.sqrt(rh + 8.313659))
+ math.atan(t + rh) - math.atan(rh - 1.676331)
+ 0.00391838 * rh ** 1.5 * math.atan(0.023101 * rh)
- 4.686035)
def thi(t, rh):
return 0.85 * t + 0.15 * wet_bulb(t, rh)
def thvi(t, rh, v):
# velocity correction of the Tao and Xin form; v in m/s
return thi(t, rh) * (max(v, 0.2) ** -0.058)
The wet-bulb approximation is accurate to a few tenths of a degree across normal shed humidity. That is better than the humidity sensor feeding it, so the formula is not the weak link.
Air Speed Is the Cheapest Cooling You Can Buy
Moving air does two things for a bird. It carries away the warm layer around the feathers, and it speeds up evaporation from the airways. The same extension guidance that gives the 15-watt figure states that an air speed of 3 metres per second, the kind tunnel ventilation produces, removes heat about three times as effectively as the near-still 0.3 metres per second of a closed, poorly ventilated shed.
The velocity-corrected index puts numbers on this for the monsoon afternoon.
Air speed at bird height | Effective index at 31 °C and 85% |
0.2 m/s, still air | 33.7 |
0.5 m/s | 31.9 |
1.0 m/s | 30.7 |
2.0 m/s | 29.5 |
2.5 m/s | 29.1 |
3.0 m/s | 28.8 |
Going from still air to 2.5 metres per second takes almost five points off the effective index, which is more than the difference between the monsoon afternoon and the night after rain. For the dry 38-degree afternoon, the index falls from 39.2 in still air to 33.9 at 2.5 metres per second.
Two practical consequences follow. First, air speed has to be measured, not assumed from the fan count. A tunnel shed with dirty shutters, slipping belts, a torn curtain or an open door at the wrong end can deliver half its design speed, and the controller will never know. Second, air speed at bird height is what matters, not at the fan. The speed varies along the shed and drops in the corners, so a single anemometer near the fans tells you about the fans, not the birds.
Measure air speed where the birds are, not where the fans are. A tunnel that is not delivering its design speed is the commonest silent failure in a hot shed.
When Pads Help and When They Hurt
Evaporative pads cool the incoming air by evaporating water into it. The best they can do is bring the air down to its wet-bulb temperature, and real pads reach a fraction of that, often quoted as 70 to 80 percent of the possible drop when they are clean and fully wetted. The script models a pad at 75 percent efficiency.
Outside air | Outside THI | Air after the pad | Humidity after the pad | THI after the pad |
38 °C, 25% | 35.7 | 26.7 °C | about 73% | 26.2 |
31 °C, 85% | 30.7 | 29.4 °C | about 96% | 29.3 |
On the dry afternoon the pad is a powerful tool: it takes about nine points off the index. On the monsoon afternoon it takes off about one and a half points, and it pushes the air to near saturation. The bird then loses most of its evaporative route for a gain of about a degree and a half in air temperature. Whether the pad helps at all on that afternoon depends on air speed and on the bird's weight, and many growers turn pads off above a humidity limit for exactly this reason.
The lesson for the controller is that the pad decision needs humidity as an input. A controller that switches pads on at a temperature set-point will run them hardest in the conditions where they do least good and most harm. A sensible rule enables pads only when the outside wet-bulb depression, the gap between dry-bulb and wet-bulb temperature, is large enough to deliver a useful drop, and disables them above an inside humidity limit that your integrator or flock adviser sets.
What to Measure, Where, and How Often
Once the index is the control variable, the sensor list follows from it. The table gives a working set for a tunnel-ventilated broiler shed. Quantities and positions are a starting point to adapt to the shed's length and layout.
Quantity | Why it matters | Where | How many | Sample rate |
Air temperature | Main input to the index | Bird height, front, middle and back, away from heaters and walls | 3 to 4 per shed | 1 min |
Relative humidity | Wet-bulb and pad decisions | Same positions as temperature | 2 to 3 per shed | 1 min |
Air speed | Velocity correction, tunnel health | Bird height, middle and back of the tunnel | 2 | 1 min |
Outside temperature and humidity | Pad decision, minimum ventilation | Shaded, ventilated screen outside | 1 | 1 min |
Ammonia | Air quality, minimum ventilation | Bird height, middle of the shed | 1 to 2 | 5 min |
Carbon dioxide | Air quality, minimum ventilation | Bird height | 1 | 5 min |
Static pressure | Inlet and curtain health | Across the end wall | 1 | 1 min |
Water meter | Early warning: birds drink more when hot | Main water line | 1 | 15 min |
Fan and pad states | Confirms the controller's commands happened | Contactor auxiliary contacts or current sensors | Per stage | On change |
Two items on that list are not climate sensors at all and are the most useful on the farm. Water consumption rises with heat before mortality does, so a jump in water use against the same day last week is an early warning that needs no calibration. Fan state feedback tells you whether a fan the controller switched on is running; a contactor that pulled in on a fan with a broken belt reports success while the fan sits still, so current sensing on the motor is better than an auxiliary contact.
Sensors That Lie in a Shed
A broiler shed is a hard place for electronics. Dust, ammonia, high humidity, washdown water between flocks and radiant heat from the roof all work against the sensors. Each fails in its own way.
Temperature probes read high when they see radiant heat. A probe hung near a roof sheet in the afternoon sun, or in the beam of a brooder, reads the surface it can see as much as the air around it. A simple radiation shield and a position at bird height fix most of this.
Relative humidity sensors drift in ammonia and saturate in condensation. Capacitive humidity sensors are the usual choice, and many datasheets warn against long exposure to ammonia and other chemical vapours. After weeks in a shed some read several points high or low, and a sensor that has been wet may read near 100 percent for hours after the air has dried. Plan to check humidity sensors against a reference every flock and to replace their filters or caps on a schedule, and prefer parts with a protective membrane.
Ammonia sensors drift and cross-react. Electrochemical cells are common, they age, and they respond to other gases. Their job in this system is a trend and an alarm, not a laboratory measurement, so calibrate them between flocks and watch the trend.
Air speed sensors clog with dust. Hot-wire and hot-film types are sensitive and fragile, and dust changes their response. Vane types are rugged but need a minimum speed to turn. Clean them between flocks and compare them with a handheld meter.
Every shed sensor drifts. Design for a check between flocks, and treat any sensor that has not been checked since the last cleanout as suspect.
The broader lesson is the same one we drew for vision systems in a shed: the environment wins against any sensor that was chosen for a clean room. Choose for the shed, plan the check, and log enough raw data to notice when a sensor starts to disagree with its neighbours.
The Ventilation Stages, Written as a Control Problem
Broiler ventilation is usually described in three or four modes, and it helps to see them as stages on one scale.
Minimum ventilation runs a small number of fans on a timer or continuously, with inlets along the side walls, to remove moisture, ammonia and carbon dioxide while holding heat. It is the mode for young birds and cool nights.
Transitional ventilation runs more fans through the side inlets, mixing incoming air above the birds so it warms before it reaches them. It bridges the gap between holding heat and removing it.
Tunnel ventilation closes the side inlets and pulls air the length of the shed from one end to the other, so the birds feel a steady wind. It is the mode for hot weather and heavy birds.
Evaporative pads add cooling to tunnel mode when the outside air is dry enough for them to help.
The controller's job is to choose the stage and the number of fans within it. The input should be the effective index, adjusted for bird age, because a seven-day chick and a 40-day broiler need very different conditions. Breed management guides publish target temperatures by age, and those targets move the whole set of thresholds down as the flock grows.
Staging Fans Without Chatter
A naive controller compares the index with a set of thresholds every minute and switches to whatever stage the comparison says. Sensor noise of a few tenths of a degree is enough to make it flip between two stages every minute near a threshold. Contactors wear, fans start and stop, side inlets hunt open and closed, and the birds see gusts instead of a steady breeze.
Two rules fix it. Each stage switches on at one value and off at a lower one, so the index has to fall well below the threshold before the stage drops. And each stage must stay for a minimum dwell time before the controller may change it again. The code below implements both.
typedef struct { float on_at, off_at; } stage_t;
static const stage_t STAGES[] = { /* illustrative set-points */
{27.0f, 26.0f}, /* 1: minimum ventilation, continuous */
{28.5f, 27.5f}, /* 2: transitional */
{30.0f, 29.0f}, /* 3: tunnel, half the fans */
{31.5f, 30.5f}, /* 4: tunnel, all fans */
{32.5f, 31.5f}, /* 5: pads enabled */
};
#define NSTAGE (int)(sizeof STAGES / sizeof STAGES[0])
#define MIN_DWELL_S 120
typedef struct { int stage; int dwell_s; } ctl_t;
int ctl_step(ctl_t *c, float index, int dt_s)
{
c->dwell_s += dt_s;
if (c->dwell_s < MIN_DWELL_S) return c->stage;
if (c->stage < NSTAGE && index >= STAGES[c->stage].on_at) {
c->stage++; c->dwell_s = 0;
} else if (c->stage > 0 && index <= STAGES[c->stage - 1].off_at) {
c->stage--; c->dwell_s = 0;
}
return c->stage;
}
We tested it against a simulated ten-hour afternoon: the index rises from 25 to 34 and falls back, sampled once a minute with a repeating noise pattern of up to 0.4 degrees. The staged controller climbed to stage 5, came back to stage 0, and changed stage 10 times in all, once per threshold in each direction. A plain threshold comparison on the same trace changed stage 216 times.
The set-points in the table are illustrative, and the pad stage in a real controller is gated by the humidity rule from the previous section. The structure is what matters: hysteresis of about a degree, a dwell of a couple of minutes, one step at a time.
Minimum Ventilation: The Cold-Night Half of the Problem
Heat stress gets the attention because it kills quickly. The cool, humid night does slower damage. With fans at their minimum, moisture from the birds and the drinkers builds up in the litter, wet litter releases ammonia, and ammonia damages the birds' airways and eyes and raises disease pressure.
Guidance for air quality in broiler housing commonly sets limits of ammonia below 25 parts per million and carbon dioxide below 2,500 parts per million, and extension advisers recommend ventilating enough to hold ammonia at 20 parts per million or less. Moisture, not temperature, is usually what minimum ventilation has to remove, and there is a direct trade between fresh air and fuel or heat.
Three things improve minimum ventilation. Run it on a timer cycle with enough on-time to exchange the air, and let the ammonia and carbon dioxide readings increase the cycle when they rise. Keep the shed tight, so the incoming air enters through the inlets, travels along the ceiling and mixes before it falls to the birds. And watch humidity inside against humidity outside: if the inside air is much wetter, the exchange is too small.
A sensor system that only alarms on heat is half a system. The same sensors, read differently, run the night.
Alarms That a Farm Manager Will Not Mute
An alarm is useful only if someone acts on it at two in the morning. Alarms that fire often for no good reason are muted within a week, and then the one that matters goes unheard.
Alarm | Trigger | Delay before alerting | Who gets it |
Heat emergency | Effective index above the top stage for 10 minutes with all stages running | 10 min | Manager and supervisor, by call |
Ventilation failure | Fan commanded on but no motor current | 2 min | Supervisor, by call |
Power failure | Mains lost and generator not running | Immediate | Manager and supervisor, by call |
Air quality | Ammonia above limit for 30 minutes | 30 min | Supervisor, by message |
Water | Consumption 30% above the same hour yesterday | 1 h | Supervisor, by message |
Sensor fault | Reading out of range, flat for an hour, or far from its neighbours | 1 h | Maintenance, by message |
The delays and percentages are starting values; tune them to your sheds. The design principles are fixed. Alarm on the outcome, such as the index staying high with everything running, not on one sensor crossing a line. Confirm that commands took effect by measuring motor current. Send the urgent alarms as a phone call, because a message on a sleeping phone is not an alarm. And separate sensor faults from climate alarms, so a dead probe does not wake the manager.
Power Cuts: Design for the Fan That Stops
In much of rural India the most dangerous event in a shed is not the weather but the power supply. A tunnel shed full of heavy birds on a hot afternoon has very little margin once the fans stop, and a generator that fails to start turns a routine outage into a loss.
The controller cannot stop a power cut, but it can make the outcome less severe.
Know immediately. Monitor mains and generator separately, and alarm by phone the moment both are down.
Fail to a safe state. Curtains and inlets that open on power loss, by gravity or spring, let natural airflow reach the birds. A curtain that stays shut because its motor has no power is the worst case.
Start in steps. When power returns, bring fans on in stages a few seconds apart, so the generator or the supply does not see every motor start at once.
Keep the controller alive. A small battery for the controller and its modem means the alarm goes out and the event is logged even while the fans are down.
Test the generator under load. A weekly start with no load proves very little. Test it on the real fan load at a quiet time.
None of this needs new sensors. It needs the electrical design and the controller logic to assume that power will fail on the worst afternoon of the year.
A Six-Shed Rollout Plan
A farm with several sheds can move to index-based control without risking a flock, by changing one shed at a time and running the old controller in parallel at first.
Instrument before you control. Install the sensor set in one shed and log for a full flock with the existing controller still in charge. Compare the index with mortality, water use and bird behaviour. This gives you the farm's own baseline.
Check every sensor against a reference. Use a calibrated handheld thermometer, humidity meter and anemometer at the sensor positions at least weekly during that flock.
Measure the tunnel. Walk the shed with an anemometer at bird height with all tunnel fans running. If the speed falls well short of design, fix the fans, shutters and curtains before touching the controller.
Run the new logic in shadow. Let the new controller compute stages and log what it would have done, while the old one still switches the fans. Review the disagreements.
Hand over control in one shed. Switch the shed to the new controller with conservative set-points and the alarm table above. Keep the old controller wired as a fallback for one flock.
Roll out shed by shed. Move to the next shed only after a full flock in the first, and keep a log of set-point changes with reasons.
At each step the farm manager should be able to see the index, the stage and the reason for each change on a phone. A controller that explains itself gets trusted; one that does not gets overridden by hand on the first hot afternoon.
Reading One Flock of Data
The first flock with the sensors in place is worth more than any set-point table, because it shows how this shed, on this farm, responds to weather. The review at the end of that flock takes an afternoon, and it answers four questions.
First, did the index track the birds? Plot the daily maximum of the effective index against the day's water use per thousand birds and the mortality count. In most sheds the three move together, with water use rising first. If mortality rose on days when the index looked comfortable, a sensor is wrong or sits in the wrong place; check the probe positions before trusting any threshold.
Second, where in the shed is the problem? Compare the front, middle and back sensors during tunnel mode. A rise of a degree or two from the pad end to the fan end is normal, because the air picks up the birds' heat as it travels. A much larger rise, or a back section that stays still, points to leaks, blocked inlets or too few fans for the shed length.
Third, how often did the controller change stage, and did it ever run out of stages? A controller sitting in its top stage for hours with the index still climbing has no more cooling to offer; that shed needs more fan capacity, better pads or lower stocking in the hottest months, not a new algorithm.
Fourth, what happened at night? Look at ammonia, carbon dioxide and inside humidity during the coolest hours. Values that creep up night after night mean minimum ventilation is too small, and the litter will show it before the birds do.
Question | What to plot | What a problem looks like |
Did the index track the birds? | Daily maximum index, water use, mortality | Mortality rises while the index looks comfortable |
Where in the shed? | Front, middle and back temperature in tunnel mode | A large rise from pad end to fan end, or a still back section |
Did cooling run out? | Hours per day in the top stage | Index still climbing with every stage running |
Is the night under control? | Ammonia, carbon dioxide and humidity, 22:00 to 06:00 | Values creeping up night after night |
Do the sensors agree? | Each sensor against its neighbours and the handheld check | One sensor drifting away from the others |
The first flock is a measurement, not a test of the controller. Change one thing at a time after it, and keep a note of why.
A short written summary of these four answers, with the plots, is also the document to put in front of an integrator, an insurer or a lender. It turns "the shed was hot" into evidence: the index, the hours above it, the equipment state and the outcome.
When an Index-Based Controller Is the Wrong Tool
Not every shed needs this. An open-sided shed with curtains and no fans has nothing for the controller to stage; there, the useful system is monitoring and alarms, so the manager can drop curtains, start foggers or reduce stocking before a hot spell.
A small flock in a backyard or a village shed does not justify the sensor set or the cost. A single temperature and humidity logger with a phone alert covers most of the value.
A farm with no reliable power backup should spend on the generator, its changeover and its testing before it spends on a better controller. A sophisticated control loop with no power behind it fails on the same afternoon as a simple thermostat.
And where the integrator supplies the controller and its settings under contract, the right move is to add monitoring and evidence, not to replace their logic. Logged indices, water use and fan currents make for a much better conversation with the integrator than a complaint about a bad night.
Back to the 31-Degree Afternoon
The wall thermometer was right. It was 31 degrees. It was the wrong measurement to control on. The air was close to saturated, the tunnel was delivering less than its design speed, and the pads may well have been making the air wetter still. On the index, that afternoon was as hard on the birds as the dry 38-degree day, and the dry day had strong airflow while the monsoon afternoon did not.
Measure temperature, humidity and air speed where the birds are, combine them, and stage on the result with patience built into the logic. Then give the cold, wet night the same care, and design for the afternoon when the power goes. The birds will tell you whether it worked long before the mortality count does.